Fujitsu · Air Conditioners
This error occurs when the inverter output DC voltage is higher than 420V for over 3 seconds. If this condition repeats 5 times, the compressor stops permanently. The outdoor unit shows no indication.
Click steps to track your progress.
Check for any external causes like voltage drops, momentary power failures (defective contacts, leak current), or noise-causing equipment (neon bulbs) in the same circuit.
Ensure complete insulation of the grounding connection.
Check all connectors for removal, erroneous connection, or open cables. Correct any issues and reset the power.