Fujitsu · Air Conditioners
This error occurs when the Input Current sensor detects 0A while the Inverter Compressor is operating at higher than 56rps, 1 minute after starting (except during defrost). The outdoor unit shows no indication.
Click steps to track your progress.
Reset the power supply to the air conditioner and observe if the error indication shows again.
Check for external causes like voltage drops, momentary power failures, or noise-causing equipment in the same circuit. Ensure proper grounding insulation.
Check all connectors and terminals for removal, looseness, erroneous connection, or open cables. Correct any issues and reset the power.