What does 60 mean?

This alarm code is displayed when the gas valve for gas heat section 2 is energized and then de-energized three times (default setting) during a single heating demand.

Common Causes

  • Intermittent issues with the gas valve in section 2.
  • Faulty ignition or flame sensor in section 2.
  • Parameter 73 (MAX GV SENSE OCC) may be set too low.
  • Inconsistent heating demand signal for section 2.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check the setting of Parameter 73 (MAX GV SENSE OCC) for the number of allowed occurrences.

  2. 2

    Inspect the gas valve and related ignition components in section 2.

  3. 3

    Ensure consistent heating demand signals for section 2.

  4. 4

    Consider adjusting Parameter 73 if appropriate and understood.