The outdoor unit LED blinks 2 times with a 2.5-second pause. The unit stops and restarts 3 minutes later, repeatedly, due to overcurrent protection (large current flowing into the power module).
Click steps to track your progress.
Turn off the power to the unit at the circuit breaker.
Reconnect the compressor's connector securely.
Check the stop valve to ensure it is in the fully open position.
Restore power and monitor if the unit cycles normally. If not, professional service may be needed to check the inverter/compressor.