Mitsubishi Electric · PWFY Air Conditioners
The unit detects a discharge temperature of 115°C (239°F) or higher multiple times (three detections within 30 minutes), leading to an abnormal stop. A preliminary error code will appear on the LED.
Click steps to track your progress.
Check that the heat vent outlet (located on the left side of the unit) is not clogged or obstructed.
Verify the circulating water supply to ensure there is no shortage and that the pump meets the required specifications.
Check the inlet air temperature on the LED monitor, if available, for unusual readings.
If the issue persists, a technician should inspect for refrigerant leaks and check the LEV operation and thermistor (TH11).