Mitsubishi Electric · PWFY Air Conditioners
When the compressor starts from Stop Mode, if low pressure reads 0.098 MPa (14 psi) immediately before start-up, the operation stops. This indicates a problem with low pressure in the system.
Click steps to track your progress.
Check the circulating water supply to ensure there is no shortage and that the pump meets the required specifications.
Inspect the low-pressure sensor cable for any visible damage, torn insulation, or disconnections.
Verify the low-pressure sensor connector for missing pins or poor contact.
Look for signs of refrigerant leakage, which can cause an inner pressure drop.
If no visible issues are found, the low-pressure sensor or controller board may need professional assessment.