NIBE · SMO 20 Control Module
The system incorrectly shows a sensor error for BT25, even when this sensor is not physically connected. This prevents proper system operation and could be a software bug related to sensor detection.
Click steps to track your progress.
Verify the BT25 sensor is correctly and securely connected to the control module.
If the sensor is intended for use, ensure it has been connected for at least five consecutive seconds.
Update the NIBE SMO 20 firmware to version 8700R4 or later.
If BT25 is not installed, ensure its function is deactivated in the system settings.