York · Smart Equipment Control
This alarm occurs when 24 VAC power is lost from the HPS2 terminal, indicating a high-pressure condition in refrigeration circuit 2. Multiple occurrences within an hour will cause a hard lockout.
Click steps to track your progress.
Connect pressure gauges and check suction and discharge pressures for refrigeration circuit 2.
Clean or clear any blockages in the condenser coil.
Verify the condenser fan and low ambient control are functioning correctly.
If a split system, check that solenoid valves are energized and opening.
Ensure the SEC board is properly configured.
Check system charge, liquid line filter, and TXV operation.