Grundfos · MAGNA3 Circulator Pumps
There is no water present at the pump's inlet, or the water contains too much air. This alarm has caused the pump to stop and does not automatically reset.
Click steps to track your progress.
Ensure the system has sufficient water supply and that all isolation valves are fully open.
Prime the pump by filling it with water to remove air.
Vent the pump and the system to eliminate any trapped air before attempting a new startup.
Check that the pump is now operating correctly; if not, contact Grundfos Service.