This alarm signifies that the Evaporator Coil 1 (EC1) sensor has failed, either due to an open circuit or by providing readings outside its expected range. This sensor protects the compressor from freezing.
Click steps to track your progress.
Check the EC1 sensor reading via the Map Gateway tool ('Details' > 'Service' > 'Inputs' > 'CoilSensors').
Unplug the EC1 sensor wires from the SEC board and measure the resistance of the wires to the sensor. Compare this to a resistance chart for the expected temperature.
If the resistance reading is incorrect, trace the wires from the plug to the sensor and perform the resistance check again.
If the wiring harness is damaged, replace or repair it. If the harness is fine, replace the sensor. If both are functional, replace the SEC board.