CodeRegistry
Brands
  1. Home
  2. York
  3. Smart Equipment Control
  4. HS3 Off Due to Gas Valve
About·Privacy·Terms

CodeRegistry — Your global library for technical solutions.

For your safety: always follow the equipment manufacturer’s official manuals. CodeRegistry is an independent help site and is not affiliated with the brands listed here.

HS3 Off Due to Gas Valve

HS3 Off Due to Gas Valve alarm

York · Smart Equipment Control

What does HS3 Off Due to Gas Valve mean?

This alarm means that heating stage 3 (HS3) is deactivated due to an issue with the gas valve. It could be related to the command signal for heating or the gas valve's operational status.

Common Causes

  • No 24 VAC power at the W3 input when heat is commanded
  • The H3 output is not commanding 24 VAC to the ignition control module
  • Problem with the 24 VAC for outputs terminal
  • Faulty ignition control module or gas valve
  • Voltage leak on the W3 terminal
  • Incorrect LV phasing if two transformers are installed

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    If using a 24 VAC input, check for 24 VAC at the W3 input when a heat command is active. If not using a 24 VAC input, verify the space temperature is below the heating set point.

  2. 2

    Check if the H3 output is commanding 24 VAC to the ignition control module. If not, check the 24 VAC for outputs terminal.

  3. 3

    If power is not present at H3 or the outputs terminal, trace the wiring for power loss. If power is present, check the ignition control module and gas valve.

  4. 4

    Verify the ignition control module is completing its sequence correctly. Check for MV feedback.

  5. 5

    If using a 24 VAC input to W3, ensure there is no voltage leak (even 0.5 VAC can cause issues).

  6. 6

    If two transformers are installed, verify the LV phasing.

Browse all codes in this manual (17)
Verified technical data. Last updated: April 2026

Related Faults

Building Pressure Sensor FailureBuilding Pressure Sensor Failure alarmC1 Locked Out Due to High PressureRefrigeration Circuit 1 High Pressure LockoutC2 Locked Out Due to High PressureRefrigeration Circuit 2 High Pressure Lockout
Source: YORK Smart Equipment Control
Open Manual (Page 14)Search more codes in this manual