Samsung Air Conditioning

94 fault codes documented

COND temperature sensor error

Condenser temperature sensor error — Outdoor coil temperature sensor fault

The condenser temperature sensor, located in the outdoor unit, is reporting an error. This sensor monitors the refrigerant temperature in the outdoor coil. This outdoor sensor error will cause the unit to turn off.

Communication error

Communication error — Indoor/outdoor inverter main MICOM communication lost

A communication error has occurred between the indoor and outdoor inverter MAIN MICOM components for at least one minute. This prevents proper system operation and displays 'Communication error'.

Communication error after tracking

Communication error after finishing tracking — System communication issue following a tracking process

A communication error has occurred after the system completed a 'tracking' procedure. This might relate to unit pairing or initial setup processes and indicates an internal communication issue.

Communication error between indoor/outdoor INV MAIN MICOM (1 min)

Communication error between main and inverter microcontrollers — Internal communication fault

This error indicates a communication failure between the main microcontroller (MAIN MICOM) and the inverter microcontroller (INVERTER MICOM) within the outdoor unit. This prevents proper operation and will cause the system to stop.

Cooling operation blocked

Cooling operation blocked — Unit cannot enter cooling mode

The air conditioner is unable to initiate or continue cooling operation due to an internal system check or a conflict in settings. This is a self-diagnostic error.

Current sensor error

Current sensor error - (No specific code given)

An unspecified current sensor error has been detected, which may affect the system's ability to monitor current draw and operate safely.

Detection of Indoor Freezing

Indoor freezing detected — Evaporator coil is freezing

The system has detected that the indoor unit's evaporator coil is freezing, which often leads to reduced airflow and poor performance. This causes the compressor to stop and triggers an outdoor unit protection control error.

Duplicated address setting error

Duplicated address setting error — Multiple indoor units have the same address

The system has detected that two or more indoor units have been assigned the same address. This causes a communication error and prevents proper operation.

E108

E108 — Duplicated communication address

Multiple indoor units within the system are configured with the same communication address, causing conflicts.

E121

E121 — Indoor room temperature sensor error (Short or Open)

The indoor unit's room temperature sensor is either short-circuited or has an open circuit, preventing accurate temperature readings.

E121, E122, E123

E121, E122, E123 - Indoor temperature sensor error (Room, EVA IN, EVA OUT)

The indoor unit's room temperature sensor (E121), evaporator inlet sensor (E122), or evaporator outlet sensor (E123) is reporting a short circuit or an open circuit. This means the sensor is not functioning correctly.

E122

E122 — Indoor EVA IN sensor error (Short or Open)

The indoor unit's Evaporator Inlet (EVA IN) temperature sensor has a short circuit or an open circuit.

E123

E123 — Indoor EVA OUT sensor error (Short or Open)

The indoor unit's Evaporator Outlet (EVA OUT) temperature sensor has a short circuit or an open circuit.

E153

E153 — Float switch error (2nd detection)

The float switch has detected a high water level in the drain pan, indicating a potential blockage or issue with the drainage system.

E154

E154 — Indoor fan error

The indoor unit's fan is not operating correctly or has encountered an error.

E163

E163 — EEPROM option error

An error has occurred with the EEPROM (memory) option settings, which may prevent proper unit operation.

E164

E164 — Incompatible outdoor unit (Wind-Free function)

An outdoor unit has been connected that does not support the Wind-Free function, causing a compatibility error.

E198

E198 — Temperature fuse error

The temperature fuse in the terminal box has disconnected, indicating a potential overheating condition or electrical fault.

E201

E201 — Indoor/outdoor communication error (Pre-tracking failure or unit quantity mismatch)

There is a communication error between the indoor and outdoor units, either during initial setup (pre-tracking) or because the actual number of indoor units differs from the outdoor unit's quantity setting.

E202

Error E202 / Communication error — Indoor and outdoor unit communication lost

The indoor and outdoor units have lost communication for at least one minute, leading to an E202 error code and stopping operation. The wired remote controller displays 'Communication error'.

E203

E203 — Communication error between indoor and outdoor units

This error indicates a problem with the communication connection or power supply between your indoor and outdoor air conditioning units. It can prevent the system from operating correctly.

E221, E231, E251, E320

E221, E231, E251, E320 — Outdoor Unit Sensor Error

These codes indicate a problem with one of the temperature or pressure sensors in the outdoor unit. E221 relates to the outdoor unit temperature sensor, E231 to the condenser (COND.) sensor, E251 to the discharge sensor, and E320 to the OLP sensor.

E403

E403 — Outdoor Unit Freezing Detected when Compressor Stops

This error indicates that freezing conditions have been detected in the outdoor unit while the compressor is stopped. This could be due to issues with airflow or the electronic expansion valve (EEV).

E404

E404 — Outdoor Overload Protection Control Active when Compressor Stops

This error signifies that the outdoor unit's overload protection has activated while the compressor is stopped, likely due to issues with the fan, electronic expansion valve (EEV), or temperature sensors.

E407

E407 — High Pressure Switch error or connector open

The high-pressure switch has an error or its connector is open, indicating a potential issue with refrigerant pressure.

E416

E416 — Outdoor Compressor Discharge Temperature Protection

This error indicates that the compressor's discharge temperature in the outdoor unit has reached a protective limit, possibly due to low refrigerant, a blocked valve, or a faulty temperature sensor.

E422

E422 — Pipe Blocking Error

This error suggests a blockage within the refrigerant piping system, which can severely impede the flow of refrigerant and prevent the unit from cooling or heating effectively.

E424

E424 — 3-Phase Power Cable Disconnection or Blown Fuse

This error indicates a disconnection in the 3-phase power supply cable to the outdoor unit or a blown fuse on the EMI (Electromagnetic Interference) control board. A similar 'Terminal Block Thermal FUSE error' is also indicated.

E425

E425 — Reverse phase or open phase (3-phase)

The 3-phase power supply to the outdoor unit has a reverse phase (incorrect phase sequence) or an open phase (one or more phases missing).

E440

E440 — Heating Not Possible: Outdoor Temperature Exceeds 30°C

This is not a product fault but a protection feature. The air conditioner will not operate in heating mode when the outdoor temperature is above 30°C to protect the unit and ensure efficient operation.

E441

E441 — Cooling Not Possible: Outdoor Temperature at -5°C or Below

This is a product protection feature. The air conditioner will not operate in cooling mode when the outdoor temperature is -5°C or colder to protect the unit and ensure efficient operation.

E458

E458 — Outdoor fan speed error (FAN1)

The system has detected an error with the operation or speed of the outdoor unit's Fan 1.

E458, E475

E458, E475 — Outdoor Unit Fan Error

These codes indicate a problem with the outdoor unit's fan, which is essential for dissipating heat and proper operation of the air conditioner.

E461

E461 — Inverter compressor operation failure

This error indicates that the inverter compressor in the outdoor unit is not operating correctly or has failed.

E461, E467

E461, E467 — Compressor Startup and Rotation Error

These codes indicate that the compressor in the outdoor unit is having trouble starting or maintaining proper rotation, which is vital for the refrigeration cycle.

E462

E462 — System stop due to full current control

The system has stopped operation because it detected an excessive current draw, triggering a full current control protection.

E462, E484

E462, E484 — Under-Current or PFC Over-Current Error

These errors relate to issues with the electrical current. E462 typically signifies an under-current condition, while E484 points to an over-current in the Power Factor Correction (PFC) circuit.

E463

E463 — OLP Overheating and Compressor Shutdown

This error indicates that the OLP (Overload Protection) has detected overheating, causing the compressor to stop. This often relates to issues with refrigerant flow or cooling of components.

E464

E464 — IPM Over-Current Error

This error indicates that the Intelligent Power Module (IPM) has detected an excessive electrical current, which triggers a protective shutdown to prevent damage to components.

E465

E465 — Compressor Vlimit Error

This error suggests a problem with the compressor's operating voltage limits, possibly indicating an abnormal compressor function or an issue with the inverter control board.

E466

E466 — DC Link Over-Current or Low-Voltage Error

This error indicates a problem with the DC Link voltage, specifically either an over-current condition or a low-voltage condition within the power circuit. This affects the inverter's ability to supply stable power.

E466, E483, E488

E466, E483, or E488 — Power supply or voltage sensor error

These codes indicate problems related to the power supply, DC Link voltage levels (either too low or too high), or a fault with the AC input voltage sensor. This can prevent the unit from operating correctly.

E467

E467 — Compressor abnormal rotation or unconnected wire

This error indicates that the compressor is rotating abnormally or that one of its wires is disconnected.

E468

E468 — Current Sensor Error

This error indicates a problem with the current sensor, which monitors the electrical current within the air conditioning system. This can be due to data corruption or an issue with the control board.

E469

E469 — DC-Link voltage sensor error (Short or Open)

The DC-Link voltage sensor has a short circuit or is open, or the DC LINK value is not within its normal range (280~320V).

E470

E470 — Outdoor unit EEPROM Read/Write error (Option)

There is an error when the outdoor unit tries to read or write data from its EEPROM (Electrically Erasable Programmable Read-Only Memory), possibly due to missing option data.

E471

E471 — OTP Error (Over Temperature Protection)

This error typically refers to an Over Temperature Protection fault, meaning a component has become too hot and the system has shut down to prevent damage. This might be related to internal firmware or sensor issues.

E474

E474 — IPM/PFCM Temperature Sensor Error

This error indicates a malfunction with the temperature sensor associated with the IPM (Intelligent Power Module) or PFCM (Power Factor Correction Module) in the outdoor unit, critical for power management.

E474, E500

E474, E500 — IPM temperature sensor error or IPM overheat

These errors indicate either a problem with the temperature sensor for the Inverter Power Module (IPM) or Power Factor Correction Module (PFCM), or that the IPM itself is overheating in the outdoor unit's inverter compressor.

E475

E475 — Inverter fan 2 error (FAN2)

The system has detected an error with the operation or speed of the inverter unit's Fan 2.

E483

E483 — Hardware detected DC link overvoltage

The system's hardware has detected an excessive voltage on the DC Link circuit.

E484

E484 — PFC Overload (Over current) Error

The Power Factor Correction (PFC) circuit in the outdoor unit has detected an overload or overcurrent condition.

E485

E485 — Input current sensor error (Short or Open)

The input current sensor for Inverter 1 has a short circuit or is open, detecting a problem even when the unit is stopped.

E488

E488 — Inverter input voltage sensor error

The sensor that measures the input voltage to the inverter has detected an error.

E500

E500 — Outdoor Inverter Compressor IPM Overheat Error

This error indicates that the Intelligent Power Module (IPM) for the outdoor unit's inverter compressor has overheated. This could be due to poor component assembly or restricted airflow.

E508

E508 — Smart install mode was not carried out

This error indicates that the 'installation smart install mode' was not successfully completed after the air conditioner installation. The unit will not work until this mode is completed successfully. This is not a malfunction but an indication of an incomplete setup.

E554

E554 — Gas Leakage Error

This error indicates that the system has detected a refrigerant gas leak. This is a serious issue that can impact cooling/heating performance and potentially harm the environment.

E556

E556 — Capacity Inconsistency Error

This error indicates an inconsistency in the capacity settings or model information between the outdoor and indoor units, which can prevent proper operation.

E557

E557 — DPM remote controller option error

There is an error with the option settings on the DPM (Distributed Power Module) remote controller.

E590

E590 — Inverter EEPROM Checksum error

The Inverter EEPROM (memory) has a checksum error, indicating potential data corruption or an issue with the stored configuration.

EEPROM Error

EEPROM Error — Configuration or component issue

This error indicates a problem with the EEPROM (Electrically Erasable Programmable Read-Only Memory) component or its option settings. The EEPROM stores important configuration data for the unit.

EEPROM Error / E556

EEPROM Error or Capacity Inconsistency — Internal memory or unit mismatch

This error indicates a problem with the unit's internal memory (EEPROM) or an inconsistency between the indoor and outdoor unit model settings. E556 specifically refers to a capacity inconsistency between units.

EEPROM circuit failure

EEPROM circuit failure — Internal memory fault

The EEPROM (Electrically Erasable Programmable Read-Only Memory) circuit, which stores critical settings and operating data, has failed. This is an internal component error.

Float Switch Detected

Float Switch Detected — Water overflow warning

This indicates that the float switch in the condensate drain pan has been activated, signaling that the drain pan is full of water and there's a risk of overflow.

Float Switch Detection

Float Switch Detected — Drain pan full or blocked drain

This error means the float switch has detected that the condensate drain pan is full of water, likely due to a clog in the drain line. This mechanism prevents water overflow.

HX IN/OUT Sensor Error

Indoor Unit Heat Exchanger IN/OUT Sensor Error — Open or Short circuit

This error indicates an issue with the heat exchanger inlet or outlet temperature sensors in the indoor unit. These sensors monitor refrigerant temperatures within the heat exchanger.

Heating operation blocked

Heating operation blocked — Unit cannot enter heating mode

The air conditioner is unable to initiate or continue heating operation due to an internal system check or a conflict in settings. This is a self-diagnostic error.

High pressure blockage error

High pressure blockage or complete refrigerant leakage detected

This self-diagnostic error indicates either a blockage in the high-pressure side of the system or a complete loss of refrigerant. This will prevent the unit from operating.

Indoor FAN error

Indoor fan error — Indoor unit fan motor fault

The indoor unit's fan motor is experiencing an error, which can lead to insufficient airflow and poor cooling or heating performance. This error indicates a problem with the indoor fan's operation.

Indoor Fan Error

Indoor Fan Motor Error — Fan not operating correctly

This indicates a problem with the fan motor located in the indoor air conditioning unit, which circulates air within your room. The fan might not be spinning at the correct speed or has stopped.

Indoor Fan Motor Error

Indoor Unit Fan Motor Error — Malfunction detected

This error indicates a problem with the fan motor inside the indoor unit. The fan is crucial for circulating air and proper operation.

Indoor HX Sensor Error

Indoor Heat Exchanger Sensor Error — Open or Short circuit

This error signals a problem with the temperature sensors that monitor the heat exchanger coils inside the indoor unit. These sensors are crucial for efficient operation.

Indoor Temp Sensor Error

Indoor Room Temperature Sensor Error — Open or Short circuit

This indicates an issue with the temperature sensor located inside your indoor air conditioning unit, which is responsible for measuring the room's temperature. It may be due to a faulty connection or a sensor malfunction.

Indoor floating switch secondary detection

Indoor float sensor error — Water level detection fault

The indoor unit's float sensor has detected an issue, likely indicating a high water level in the drain pan. This is a self-diagnostic error and will cause the unit to turn off.

Indoor sensor error

Indoor sensor error — Indoor evaporator pipe sensor fault

The indoor unit's evaporator (Eva In) pipe sensor is either open (disconnected) or short-circuited (faulty). This impacts the system's ability to monitor refrigerant temperatures and stops operation.

Indoor temperature sensor (open/short error)

Indoor temperature sensor error — Room temperature sensor fault

The indoor unit's room temperature sensor has an open or short circuit, meaning it cannot correctly read the room temperature. This is an indoor sensor error and will cause the unit to turn off.

Indoor unit Eva In sensor (Open/Short)

Indoor unit Evaporator Inlet sensor error — Indoor pipe sensor fault

The indoor pipe sensor, also known as the evaporator inlet sensor, has an open or short circuit. This prevents the unit from monitoring refrigerant temperature correctly and will cause the unit to turn off.

Indoor unit communication error

Indoor unit communication error — Indoor unit communication issue

The wired remote controller displays a communication error, indicating a problem with how the indoor unit is communicating with other parts of the system. This error will cause the system to turn off.

No response error address from indoor unit

No response error address from indoor unit — Indoor unit not responding

The outdoor unit is not receiving a response from one of the indoor units at its assigned address. This indicates a communication breakdown and stops the system from operating.

Outdoor Temp Sensor Error

Outdoor Temperature Sensor Error — Malfunction detected

This error indicates a problem with the temperature sensors on the outdoor unit, such as the outdoor ambient, condenser, or discharge temperature sensors. These are vital for the unit's operating logic.

Outdoor Valve Clogging

Outdoor Valve Clogging Error — High pressure detected

This error indicates that there might be a blockage in the outdoor unit's valve, leading to unusually high pressure within the system. This can affect cooling or heating performance.

Outdoor Valve Clogging Error

Outdoor Valve Clogging Error — Refrigerant line blockage

This error suggests a blockage in the outdoor valve, which can lead to high pressure in the refrigerant system and impair the unit's performance.

Outdoor fan 1 error

Outdoor fan error — Outdoor unit fan motor fault

The outdoor unit fan motor is not operating correctly, which can lead to overheating and system performance issues. This is a self-diagnostic error and will cause the unit to turn off.

Outdoor sensor error

Outdoor sensor error — Inverter emission temperature sensor fault

The inverter's emission temperature sensor is faulty or incorrectly connected. This leads to an 'Outdoor sensor error' message and prevents proper system operation.

Outdoor temperature sensor error

Outdoor temperature sensor error — Outdoor ambient temperature sensor fault

The sensor that measures the outdoor ambient temperature is reporting an error, possibly due to an open or short circuit. This is an outdoor sensor error and will cause the unit to stop operating.

Outdoor unit power not ON (3-phase)

Outdoor unit power not on — No power to the 3-phase outdoor unit

The outdoor unit, specifically a 3-phase product, is not receiving power. This prevents the entire air conditioning system from operating and requires an initial diagnosis of the power supply.

Outdoor unit protection control error

Outdoor unit protection control error — Inverter total current or PFC over current

The inverter has detected an abnormal total current or PFC (Power Factor Correction) overcurrent condition. This triggers an outdoor unit protection control error, stopping operation.

Protection of Outdoor Overload

Outdoor overload protection — Outdoor unit or compressor is overloaded

The outdoor unit has detected an overload condition, causing the compressor to stop as a protective measure. This indicates the system is under excessive strain and is an outdoor unit protection control error.

Room Temp Sensor Error

Indoor Unit Room Temperature Sensor Error — Open or Short circuit

This error means there's a problem with the temperature sensor inside the indoor unit that measures the room temperature. It could be an electrical open circuit or a short circuit.

Self diagnostic error

Self diagnostic error — Outdoor fan 1 fault

A fault has been detected with outdoor fan 1, triggering a self-diagnostic error and preventing normal operation of the air conditioner.

Thermal Fuse Open Error

Thermal Fuse Open Error — Overheating protection triggered

A thermal fuse has opened, which is a safety mechanism designed to protect the unit from overheating. This indicates that a component has reached an unsafe temperature, causing a system shutdown.

[Inverter] Compressor startup error

Inverter compressor startup error — Compressor failed to start

The inverter compressor in the outdoor unit failed to start correctly, triggering a protection control error. This prevents the system from cooling or heating.

[Inverter] Emission temperature sensor error

Inverter emission temperature sensor error — Discharge temperature sensor fault

This error indicates a problem with the emission (or discharge) temperature sensor in the inverter system, which monitors the temperature of the refrigerant leaving the compressor. This outdoor sensor error will cause the unit to turn off.

[Inverter] Total current error / PFC over current error

Inverter total current or PFC overcurrent error — Excessive current detected

The inverter system has detected an excessive total current or an overcurrent in the Power Factor Correction (PFC) circuit, triggering a protection shutdown. The unit will turn off.

Samsung Air Conditioning Fault Codes — Complete Error List | CodeRegistry